NOTICE: this is the author's version of a work that was accepted for publication in Control Engineering Practice. Changes resulting from the publishing process, such as peer review, editing, corrections, structural formatting, and other quality control mechanisms may not be reflected in this document. Changes may have been made to this work since it was submitted for publication. A definitive version will be subsequently published in Control Engineering Practice with the above DOI.
All documents in ORBi are protected by a user license.
Abstract :
[en] A two-level adaptive control scheme against power system voltage instability is proposed, to deal with emergency conditions by acting on distribution transformers and/or by curtailing some loads. The lower level includes distributed controllers, each acting once the voltage at a monitored transmission bus settles below a threshold value. The upper level benefits from wide-area monitoring and adjusts in real-time the voltage thresholds of the local controllers. Emergency detection is based on the sign of sensitivities. The proposed scheme is robust with respect to communication failures. Its performance is illustrated through detailed simulations of a small but realistic 74-bus test system.